Network of industrial pipes and valves
In-line heating of flowing fluids

Circulation Heaters

A flanged heater installed in an insulated vessel through which the fluid is pumped, heating it in-line.

Circulation heater: flanged element bundle inside a pressure vessel Cold fluid inlet Heated outlet Insulated vessel Terminal box

Schematic illustration drawn for ECC, not to scale.

01Product description

A circulation heater is a flanged immersion heater mounted inside a vessel with inlet and outlet connections. The fluid is pumped through the vessel and heated as it flows past the elements. This allows indirect heating of a tank, or direct heating of a process stream, without placing elements in the tank itself.

02Operating principle

Forced flow across the elements increases heat transfer compared with still liquid, so the heater can be smaller for the same duty. Flow rate, inlet temperature and outlet temperature define the power required; a controller modulates the heater to hold the outlet temperature.

03Industrial applications

  • Heat transfer fluid (thermal oil) systems
  • Process water and clean-in-place loops
  • Fuel oil and lubricating oil heating
  • Heating of tank contents through an external loop
  • Heating of gases and steam superheating (with designs for gas service)

04Technical characteristics

  • Flanged element bundle inside a pipe-body vessel
  • Inlet and outlet nozzles sized for the flow
  • Vessel insulation and jacket
  • Thermowells for process and over-temperature sensors
  • Vessel design to the required pressure and temperature

05Advantages

  • Compact heating of a flowing stream
  • Heater can be serviced without draining the main tank
  • Precise outlet temperature control

06Selection variables

  • Medium being heated, its chemistry and its viscosity across the temperature range
  • Required power (kW) for heat-up and for holding temperature, including heat losses
  • Operating temperature and maximum allowable sheath temperature
  • Allowable watt density for the medium and flow condition
  • Sheath material compatible with the medium and the temperature
  • Supply voltage, number of phases and circuit arrangement
  • Terminal enclosure rating for the installation area (general purpose, moisture-resistant or hazardous location)
  • Temperature control and over-temperature protection
  • Flow rate, inlet and outlet temperatures, and allowable pressure drop
  • Vessel design pressure and temperature
  • Flow interlock so the heater cannot run without flow

07Installation considerations

  • Install a flow switch or interlock: elements in a circulation heater rely on flow to remove heat.
  • Vent air and gas from the vessel before energizing.
  • Provide isolation valves for maintenance.

08Technical information

A circulation heater is sized from the flow rate and the temperature rise of the fluid passing through it.

P (kW) = ṁ (lb/h) × cp × ΔT ÷ 3,412
ṁ (lb/h) = flow (gpm) × 60 × 8.34 × SG
Water shortcut: heat (Btu/h) ≈ gpm × 500 × ΔT

SG = specific gravity of the fluid (water = 1.0).

Worked example 1 — water

10 gpm of water heated from 60 °F to 120 °F:

Heat = 10 × 500 × 60 = 300,000 Btu/h
P = 300,000 ÷ 3,412 = 87.9 kW

Worked example 2 — oil

20 gpm of oil (SG 0.87, cp 0.50 Btu/lb·°F) heated by 50 °F:

ṁ = 20 × 60 × 8.34 × 0.87 = 8,707 lb/h
P = 8,707 × 0.50 × 50 ÷ 3,412 = 63.8 kW

Add a safety factor and the losses of the piping. For thermal fluids, guidance from fluid suppliers is about 20–22 W/in² with fully turbulent flow and 10–12 W/in² without circulation.

Request information on circulation heaters

Share your application data; we will reply with the next steps and a quotation where possible.